Christmas Lights – What Would It Take To Start A Fire?

 

There’s a ton of web sites out there offering all the same basic advice on Christmas light safety; don’t use frayed cords, don’t use damaged lights, blah blah blah.  I think most people know all this stuff.  I was curious what could really pose a threat if you’re using new lights and new extension cords, so I thought I’d do a little math and figure it out.

As they say on the greatest TV show ever, WARNING: SCIENCE CONTENT.

As I see it, there are three main places for potential failure when installing Christmas lights – extension cords, power strips, and light cords.  I’m assuming the lights will be plugged in to a standard 15 amp outlet, and nothing else is running on that circuit (lighting, TVs, radial arm saws, etc).

Lights: I took a brand new string of 150 lights and examined the fine print on the warning label.  As you can see, the lights draw .54 amps.  This means that you could theoretically have 27 sets of lights plugged in to one circuit, and you would use 14.58 amps – just below the tripping point of a standard 15 amp breaker.  Each string of lights has a 3 amp fuse built in to the plug, so you could potentially have five strings of lights plugged in to each other, end to end, to get 2.7 amps.  For the record though, I’ve always heard that you shouldn’t use more than three.

Warning Label with Arrow
If you noticed the date code on the lights, you got me. These lights have been sitting in my basement for seven years. When stuff goes on clearance for 25 cents, I can't help myself!

Christmas Light Package

Power Strip: I just took a look at a cheap power strip that I had lying around in my basement, and was surprised to see that the power strip was rated for 15 amps!  This means that the power strip should be able to deal with anything I plug in to it – if I overload it, the circuit breaker in my electric panel will trip.

Extension cord: I expected this to be the weakest link, but it’s not as weak as I thought; the smallest extension cord I could find online or in the store was rated for 13 amps.  This means that if you plugged a power strip in to the end of the extension cord and ran 5 strings of lights (with 5 sets to a string), you would have a total of 25 sets pulling13.5 amps.  This could start the extension cord on fire.  Twenty-four sets of lights would probably be safe at 12.96 amps, giving you a total of 3,600 lights.
Extension Cord

The bottom line? All the blah blah blah advice you hear is right on.   As long as you’re using new lights, new extension cords and new power strips, you shouldn’t have much to worry about, and you shouldn’t have to do any math.    Just remember to read the safety labels, and do some simple calculations if you think you're using too many lights.

What if 3,600 lights isn't enough? Of course, a lot of people ask me this, and I always tell them to buy LED lights.  They're hideously expensive, but they use 80% - 90% less power.

What about the heat from the lights? Mythbusters already tried setting a Christmas tree on fire using only the heat from the bulbs.  It's impossible.  They ended up using a neon transformer to set a tree on fire.

Reuben Saltzman, Structure Tech Home Inspections – Email – Minnesota Home Inspections

Reuben Saltzman, Structure Tech Home Inspections

        

Comment balloon 18 commentsReuben Saltzman • November 26 2009 07:40AM
Christmas Lights – What Would It Take To Start A Fire?
share
There’s a ton of web sites out there offering all the same basic advice on Christmas light safety; don’t use frayed cords, don’t use damaged lights, blah blah blah. I think most people know all this stuff. I was curious what… more
Bad Chimneys Don't Always Need Repair
share
Most homes in Minneapolis and Saint Paul are old houses with masonry chimneys. When these masonry chimneys go bad (and they all go bad) the repair can be very expensive. If you call up a chimney contractor to see what can be done about… more
Forget Code, Bathrooms Need Fans.
share
For the last 800 years, building codes have allowed bathrooms to be built without exhaust fans. Exhaust fans aren't even a requirement here in Minnesota! This is a great example of how building codes are only minimum standards. I… more
Ground Fault Circuit Interrupters (GFCIs), Part 2
share
Last week I gave an overview of what GFCI outlets are for - the long and short is that GFCIs are life safety devices; they prevent lethal shocks. This week I'll talk about the different types of GFCI devices, how to test them,… more
Ground Fault Circuit Interrupters (GFCIs), Part 1
share
For this this week and next week's blogs, I'll be waxing on GFCI outlets. I'll talk about what they do, why they're so important, what you need to know about them, and how to test the outlets in your own home. First, a quick… more