Double Tapped Neutrals: This Isn't A New Rule

While I try to make most of my blog posts somewhat generic and appealing to most, this one ain't that.  This post is about a very specific electrical defect that I frequently run across, and I'm writing this post so I can give my clients a better explanantion of this defect.  Oh, and also so I can give my clients proof that this isn't some new requirement that I just heard about.

Double Tapped NeutralThe problem I'm addressing today is double tapped neutral lugs in electric panels.  A 'double tapped neutral' is another way of saying that one of the screws on the neutral bus bar in the panelboard has more than one neutral wire feeding to it.  This is a no-no, and has been for very long time.

One reason that two neutral wires can't be connected to a single terminal in a panelboard is so that the circuit can be isolated if it needs to be worked on.  There is a great explanation of this at theSchneider-Electric web site.  The other reason you can't have two neutral wires connected under a single lug is because the connections might come loose.  While panel manufacturers will allow for up to three grounding conductors under a single lug, they typically only allow one neutral wire.  The grounding conductors aren't going to normally carry current for extended periods of time, so they have a very slim possibility of coming loose.  This isn't the case with the neutral conductors. 

Despite what many seem to think, this didn't become a new requirement in 2002.  This has been a requirement of UL 67 for a long time, but was spelled out in the NEC in 2002.   Oh, and for the record, if a home inspector recommends a repair of say, a double tapped neutral, they're doing it for the reasons listed above; not because it's "code".

Reuben Saltzman, Structure Tech Home Inspections

        

Comment balloon 18 commentsReuben Saltzman • May 24 2011 06:05AM
Double Tapped Neutrals: This Isn't A New Rule
share
While I try to make most of my blog posts somewhat generic and appealing to most, this one ain't that. This post is about a very specific electrical defect that I frequently run across, and I'm writing this post so I can give my clients a… more
Should You Drain Your Water Heater?
share
I've read a lot of water heater installation manuals, and they all give the same advice on water heater maintenance, but most people don't do any type of maintenance on their water heaters, period. Today I'm going to go over the… more
Carbon monoxide alarm requirements for Minnesota, including the…
share
Carbon monoxide alarms are required in just about every type of dwelling in Minnesota, and it's been this way for several years now, but there is still a lot of confusion about this requirement. General Requirement - This text… more
How To Inspect Your Own Deck
share
As I'm sure you already know, May is Deck Safety Month, so it's a good time to talk about deck inspections. Is your own deck safe? Now is the time to check. If you're going to have a party or a large gathering, you better be sure. The… more